Issue Date: November 16, 2015
Revision Date: August 6, 2020
Franklin Fueling Systems
INCON T5 Series, TS-5,
TS-550, TS-5000, TS-550evo and TS-5000evo, Colibri, EVO 200, EVO
400, EVO
600 and EVO 6000 consoles with SCALD 3 (INCON TSP-LL2 and FMP-LL3
Magnetostrictive Probe)
CONTINUOUS IN-TANK LEAK DETECTION METHOD
(Continuous Automatic Tank Gauging)
Certification |
Leak rate of 0.2 gph with PD > 95% and PFA < 0.001%. |
Leak Threshold |
0.17 gph for single tanks at 95% PD. |
Applicability |
Gasoline, diesel, aviation fuel, fuel oil #4, biodiesel blends B6-B20 meeting ASTM D7467, biodiesel B100 meeting ASTM D6751. |
Tank Capacity |
Maximum of 32,891 gallons for single tanks and for all tanks manifolded together. |
Throughput |
Monthly maximum of 445,408 gallons. |
Waiting Time |
None. The algorithm tests the data for stability and discards those before the tank is stable. |
Test Period |
Data collection time ranges from 5 to 26 days. |
Temperature |
Average for product is determined by a minimum of 5 thermistors. |
Water Sensor |
Must be used to detect water ingress. |
Calibration |
Thermistors and probe must be checked and, if necessary, calibrated in accordance with manufacturer's instructions. |
Comments |
The user configuring the system can select between 99% and 95% PD modes. System reports a result of "pass" or "fail." |
Franklin Fueling Systems |
Evaluator: Ken
Wilcox Associates |
3760 Marsh Road |
Tel: (816) 443-2494 |
Madison, WI 53718 |
Dates of Evaluations: 09/14/15 |
Tel: (800) 225-9787 |
|
E-mail: info@franklinfueling.com | |
URL: www.franklinfueling.com |
|
| Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |
Appearance on
this list is not to be construed as an endorsement by any regulatory agency nor
is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable
laws and regulations. For full details, please refer to our expanded "DISCLAIMER"
page.