Issue Date:
July 22, 2003
Revision Date: February13, 2015
Franklin Fueling Systems
INCON
T1 Series
TS-750,
TS-1000, TS-1001, TS-2000, TS-2001,
INCON T5 Series TS-5, TS-608, TS-550,
TS-550 evo, TS-5000, TS-5000 evo,
Colibri CL6 & TS-CL6 Series with SCALD 2.0
(INCON TSP-LL2 and FMP-LL3 Magnetostrictive Probe)
CONTINUOUS IN-TANK LEAK DETECTION METHOD
(Continuous
Automatic Tank Gauging)
Certification |
Leak rate of 0.2 gph with PD > 99% and PFA < 1%.
|
Leak Threshold |
0.10 gph for single and manifolded tank systems.
A tank system should not be declared tight and a message printed for the
operator, if the test results indicate a loss or gain that exceeds this
threshold. |
Applicability |
Gasoline, diesel, aviation fuel, fuel oil #4, biodiesel
blends B6-B20 meeting ASTM D7467, biodiesel B100 meeting ASTM D6751.
|
Tank Capacity |
Maximum of 49,336 gallons for single tanks and for all tanks
manifolded together.
Tank must be between 14 and 93.5% full. |
Throughput |
Monthly maximum of 257,818 gallons. |
Waiting Time |
None between delivery and data collection when difference
between product in tank and product delivered is 6.0 degrees F or less.
|
Test Period |
Data collection time ranges from 5 to 28 days. Data sampling
frequency is > 1 per second.
System collects data at naturally occurring product levels without
interfering with normal tank operation, and discards data from unstable
periods when system performs test. |
Temperature |
Average for product is determined by a minimum of 5
thermistors. |
Water Sensor |
Must be used to detect water ingress.
Minimum detectable water level in the tank is 0.208 inch (0.44 inch using
model TSP-IGF4P).
Minimum detectable change in water level is 0.011 inch (0.013 inch using
model TSP-IGF4P). |
Calibration |
Thermistors and probe must be checked and, if necessary,
calibrated in accordance with manufacturer's instructions.
|
Comments |
System reports a result of “pass” or “fail”.
Evaluated using both single and manifolded tank systems with probes in each
tank.
Tests only the portion of the tank containing product.
As product level is lowered, the leak rate in a leaking tank decreases (due
to lower head pressure).
Consistent testing at low levels could allow a leak to remain undetected.
EPA leak detection regulations require testing of the portion of the tank
system which routinely contains product.
TS-750, TS-1000 and TS-1001 can support up to 4 tanks.
TS-2000 and TS-2001 can support up to 8 tanks.
TS-5 can support up to 12 tanks.
TS-608 can support up to 8 tanks.
TS-550,
TS-550 evo and
TS-5000 can support up to 48 tanks.
Colibri CL6 and TS-CL6 can support up to 6
tanks
TS-750 and TS-2000 do not provide fuel logistics, remote
monitoring and other business management options available with TS-1000, TS-1001, and
TS-2001.
The database for evaluation of the system includes sites with vapor recovery
and blending dispensers.
The FMP-LL3 probe may be configured to operate as an LL2 model.
|
Franklin
Fueling Systems
|
Evaluator: Ken
Wilcox Associates
|
3760 Marsh Road
|
Tel: (816)
443-2494
|
Madison, WI
53718
|
Dates of
Evaluations: 07/11/2003, 03/18/06, 08/18/09, 07/06/11, 04/09/12, 08/04/14
|
Tel: (800)
225-9787
|
|
E-mail:
info@franklinfueling.com |
|
URL:
www.franklinfueling.com
|
|
|