Issue Date: November 22, 1995
Revision Date: August 26, 2003
 

Campo/Miller, Inc.

LS300-120 PLUS AL, LS300-120 PLUS AL A/S, LS300-120 PLUS AL LSI

AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

Certification Leak rate of 3.0 gph with PD = 100% and PFA = 0%. 
Leak rate of 0.2 gph with PD = 100% and PFA = 0%. 
Leak rate of 0.1 gph with PD = 100% and PFA = 0%.
Leak Threshold 1.5 gph for leak rate of 3.0 gph.
0.1 gph for leak rate of 0.2 gph.
0.05 gph for leak rate of 0.1 gph. 
A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold.
Applicability Gasoline, diesel, aviation fuels, fuel oil #4, waste oil, kerosene. 
Other liquids may be tested after consultation with the manufacturer.
Specification System tests pressurized fiberglass, steel, and flexible pipelines.
Tests are conducted at operating pressure.
Pipeline Capacity Maximum of 163 gallons for steel and fiberglass (example: 350 feet of 3 3/8 inch line).
Maximum of 39.5 gallons for flexible piping (example: 430 feet of 1 ½ inch line).
Waiting Time None between delivery and testing. 
None between dispensing and testing for leak rate of 3.0 gph. 
Minimum of 3 hours between dispensing and testing for leak rate of 0.2 gph. 
Minimum of 6 hours between dispensing and testing for leak rate of 0.1 gph.
Test Period Response time is 10 minutes for leak rate of 3.0 gph. 
Minimum of 25 minutes for leak rate of 0.2 gph. 
Minimum of 34 minutes for leak rate of 0.1 gph. 
Test data are acquired and recorded by a microprocessor.
System Features Permanent installation on pipeline. 
Automatic testing of pipeline every 45 minutes for leak rate of 3.0 gph. 
Automatic testing of pipeline when pump has been idle for 3 hours for leak rate of 0.2 gph. 
Automatic testing of pipeline when pump has been idle for 6 hours for leak rate of 0.1 gph. 
Preset threshold.
Triplicate testing to determine if pipeline is leaking. 
Pump shutdown, indicator light and alarm activation if leak is declared.
Calibration System must be checked annually and, if necessary, calibrated in accordance with manufacturer's instructions.

 

Campo/Miller, Inc.

Evaluator:  Ken Wilcox Associates

P. O. Box 1809

Tel:  (816) 443-2494

Porterville, CA 93258

Date of Evaluation:  06/23/95, 09/10/98

Tel:  (209) 781-6862

 

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.